ZW32-12 Primary and Secondary Fused Column Circuit Breaker with Capacitor Power Extraction Type
Category: Pole-mounted Circuit Breaker
Intro: The ZW32-12 Primary and Secondary Fusion Pole-Mounted Circuit Breaker Capacitive Power Extraction Type (Measurement Control Device, Integrated Fault Isolation) is an outdoor power distribution device used in 12kV voltage and three-phase AC 50Hz, mainly used for breaking overload current, short-circuit current, and automated devices for line fault detection, diagnosis, and handling. Integrated design of the switch body, power access unit, measurement unit, and control unit: features simple installation and convenient maintenance, making it a device for automated feeder system for distribution lines.

Product Overview

The ZW32-12 Primary and Secondary Fusion Pole-Mounted Circuit Breaker Capacitive Power Extraction Type (Measurement Control Device, Integrated Fault Isolation) is an outdoor power distribution device used in 12kV voltage and three-phase AC 50Hz, mainly used for breaking overload current, short-circuit current, and automated devices for line fault detection, diagnosis, and handling. Integrated design of the switch body, power access unit, measurement unit, and control unit: features simple installation and convenient maintenance, making it a device for automated feeder system for distribution lines.

The circuit breaker is equipped with a unified standardized current-voltage integrated sensor, featuring a wide measurement range, high accuracy, and high reliability. It offers comprehensive analog data and accurately determines various line faults.

Citation Standards:

IEC56-427 "High Voltage AC Circuit Breaker"

GB/T1984-2014 "High Voltage AC Circuit Breaker"

GB/T11022-2011 "Common Technical Requirements for Standards for High Voltage Switchgear and Control Equipment"

SD132-89 "Technical Specifications for High-Voltage AC Circuit Breakers"

GB/T13384-1992 "General Technical Conditions for Packaging of Electromechanical Products"

DL/T402-2016 "High Voltage AC Circuit Breaker Ordering Conditions"


Model and meaning

1-1.jpg


Main technical parameters

Main technical parameters of the circuit breaker

Project nameUnitTechnical specifications
Rated voltagekV12
1 min power frequency withstand voltage UdkV42 alternating and ground-to-ground sections, 48 fractures
Rated Impulse Withstand Voltage Up (Peak)kVAlternating and ground-to-ground 75, fracture 85
Rated current AA630
Rated short-circuit breaking currentkA20、25
Rated short-circuit breaking current number of breaksTimes≥ 30
Rated short-circuit closing current (peak value)kA50、63
Rated peak withstand currentkA50、63


Mechanical characteristic parameters of circuit breakers

Project nameUnitTechnical specifications
Rated short-term withstand currentkA20、25
Rated short circuit durations4
Rated operation sequenceO-0.3s-CO-180s-CO
Mechanical lifespanTimes≥ 10000
Rated operating voltageVDC24
Energy storage time at rated voltages<10
Partial dischargepC≤ 10(14.4KV)


Technical parameters of voltage transformers

Project nameUnitTechnical specifications
Contact head spacingmm9±1
Contact overtravelmm2±0.5
Average gate opening speedm/s1.2±0.2
Average closing speedm/s0.7±0.2
Contact closing bounce timems≤ 2
Three-phase closing has different phasesms≤ 2
Three-phase sluice gates have different phasesms≤ 2
Closing time (electric)ms≤ 50
Opening time (electric)ms≤ 45
DC resistor in the main circuit of each phaseμΩ≤ 80
The interphase center distancemm340


Technical parameters of voltage transformers

Project nameTechnical specifications
Rated voltage ratioPhase sequence: (10/√3)/(3.25V/√3) Zero sequence: (10/√3)/(6.5V/3)
Implementation methodsCapacitive voltage divider
Accuracy levelPhase sequence: 0.5 order, zero sequence 3P class
Temperature range-40~ 50℃
Insulation resistance (to ground)>1000MΩ
Load impedance≥ 5MΩ


Main technical parameters of the circuit breaker

Project nameTechnical specifications
Rated current ratioPhase sequence: 600A/1V, zero sequence: 20A/0.2V
Implementation methodsLow power electromagnetic type
Accuracy levelPhase sequence: 0.5s/5P 10 levels, zero sequence 1/10P 10 levels
Temperature range-40~ 50℃
Load impedance≥ 20kΩ


Operating environment conditions

Ambient temperature: temperature 50°C, low temperature -40°C. Daily temperature difference 35K;

Relative humidity: daily average <95%, monthly average <90%;

Altitude: below 3000m:

Wind speed: not exceeding 35m/s (equivalent to air pressure 700Pa);

Pollution level: Level IV;

Ice coating thickness: 10mm;

Locations free from fire, explosion, chemical corrosion, and frequent severe vibrations;

Note: When the usage environment differs from the above application environment, consultation between the user and the manufacturer is required.


Product structural design and dimensions

2.jpg